(Susol) Molded Case + (Noark) Branch & Supplementary breakers



Susol and Noark breakers are stocked in our Edmonton, Alberta, Canada facility.

Noark - Branch & Supplementary
dinrail mountable Breakers

 

EX9 B1N are 240 volt rated Branch Circuit breakers.

EX9 B1H are 277/480 volt rated Branch Circuit breakers.

EX9 B1E are 277/480 volt rated Supplemental Breakers.

Finally - Control circuit & molded case branch breakers at an affordable price!!

The following are just a few $$ examples -

a) B1N1D15 (1-pole, 15A, 240v, 10ka) branch breaker- $18.50
b) B1H1D15 (1-pole, 15A, 277/480v, 10ka) branch breaker - $18.50
c) B1E1D15 (1-pole, 15A, 277/480v, 10ka) supplemental breaker - $11.00

Prices are subject to change without notice.

Noark EX9 B1H dinrail mountable branch breaker

Noark EX9 B1H Features:

• Complete range of UL 489 listed miniature circuit breakers up to a 63A current rating

• Breakers mount on standard 35 mm DIN rail

• Standard ratings of 10 kA at 480Y/277 Vac and 10 kA at 125 Vdc

• Suitable for branch circuit device protection

• Trip-free design — breaker cannot be defeated by holding the handle in the ON position

• Captive screws cannot be lost

• For use in applications for which UL 1077 or CSA C22.2 No.235 are also allowed

• Field installable shunt trip and auxiliary switch subsequent mounting

• Available with provisions for ring tongue terminals

• Module width of only 18 mm (per pole)

• Contact position indicator (red/green)

• Possibility for locking the toggle in ON or OFF position

Noark EX9 Series B1 PDF: EX9 B1

Complete Noark catalogue: Noark

 

Noark Application Solutions:

Conformed Standard: UL 489
Certifications: IEC/EN 60947-2, CE Approved, UL Listed, CSA Certified and RoHS Compliant
Rated Operational Voltage (V): 480/277 Vac
Rated Frequency (Hz): 50/60 Hz
Rated Current (A): 0.5~20
Number of Poles: 1, 2 & 3
Rated Insulation Voltage (V): 500
Rated Impulse Withstand Voltage (kV): 6
Instantaneous Tripping Type: C, D
Interrupting (kA): SEE CATALOG
Inverse Time-Delay Over-Current Release Type: Thermal-Magnetic
Service Life - Electrical: 6000
Service Life - Mechanical: 10000
Protection Degree: IP20
Wire: 14~4 AWG (single wire); 14~6 AWG / 14~10 AWG (two wires)
Testing Ambient Air Temperature Range: 23ºF to 104ºF (-5ºC to +40ºC)
Working Ambient Air Temperature Range: -13ºF to 131ºF (-25ºC to +55ºC)
Insulation Coordination - Rated Insulation Voltage: 500 Vac
Insulation Coordination - Rated Impulse Withstand Voltage: 6 kV
<b>Pollution Degree: Class 3
Over Voltage Category/Mounting: Class III / 35 mm DIN rail
Altitude: Does not exceed 2000m
Atmospheric Conditions: At +20ºC, the relative humidity does not exceed 90%; At +40ºC, the relative humidity does not exceed 50%

 

____________________________________
_______________________________

Susol (MCCB) Molded Case Circuit breakers
For protection of p
ower distribution.

Susol (MCCB) Molded Case Switch
For protecting and disconnecting circuits

 

Especially for Panel Builders - Consider Susol Main and/or branch breakers along with their through-door or flange mounted operators. When you consider the cost of Susol, you will really wonder why the other manufacturers of molded case breakers are so costly in comparison.



Panel Building?

Susol has both through-door extended rotary handle operators (shown to the right) and flexible cable flange mounted operators.

Susol is considerably more cost-effective than any of its competitors.

If you are a panel builder, then you have seen the high cost of Wesco, GE, Stromberg, Cutler-Hammer, and others, almost to the point that a panel builder will generally not install the main breaker in their panel and leave the installation electrician install an overcurrent protection device (or disconnect means) ahead of the panel.

 

 


Susol Molded Case breakers and through-door rotary operator.

Susol molded case and Noark branch & supplemental breakers are stocked in our Edmonton, Alberta, Canada facilit

 

 

Here's just an example of pricing for Susol;

a) TD125NU-FTU-LL 125, MCCB - 3 Pole Circuit Breaker, 35kA, 125 Amp, 600v, Fixed Thermal & magnetic, complete with Line & Load lugs ... $322

b) EHX12,  12" Extended Rotary Disconnect handle assemblyfor TD125 Amp Breaker with NEMA 4 Gasket .... $95

Prices are subject to change without notice.

For a complete PDF of Susol molded-case breakers, press HERE.

 

 ======================================================================  

Distributed by; Electram Rotary Equipment Ltd
, 18112 - 107th Avenue,

Edmonton, Alberta, Canada,
T5S 1K5

Part of the PhaseMAXX Power Products Group.